5 Install Rack Options 31
Install a Paradigm Repeater or Dual Repeater Module
Both repeater module types may only be utilized in the top module slots of the ERn4 rack
enclosure.
The Paradigm Station Repeater (P-REP) module extends the system station bus length by
1,640 feet (500m) and adds support for up to 30 additional stations.
The Paradigm Dual Station Repeater (P-DREP) module extends the system station bus
length 3,280 feet (1,000m) through two separate topology-free Echelon segments (each
supporting 1,640 feet (500m) of additional LinkPower station wire each) and adds support
for up to 30 additional stations.
The following table lists the recommended control wire types used in a typical Unison
installation and the maximum wire runs allowed.
Purpose
Link Power
(Belden 8471)
DMX (Belden
9729)
Ethernet
(Cat5 /Belden
1583a)
Feet Meter Feet Meter Feet Meter
Total length of control wire
(without repeater module)
1640 500 1600 487 328 100
Maximum wire length (ERn
to station)
1313 400 1600 487 N/A N/A
Maximum repeater distance
1640 500 N/A N/A N/A N/A
Blank (Air flow) module (ERn-BM)
Paradigm Station Repeater module (P-REP)
Paradigm Station Power Module (P-SPM)
Paradigm Architectural Control
Processor (P-ACP)
Paradigm Dual Station Repeater module (P-DREP
Paradigm Station Power Module (P-SPM)
Paradigm Architectural Control Processor (P-
ACP)
Comentarios a estos manuales