7
b) The bypass switch shall be used when no DMX devices are present at that
location. When activated, the DMX pass through switch shall pass DMX directly
through to the next DMX panel on the strip. The pass through switch shall have a
mechanical indicator to show the operator that it has or has not been engaged
8) Connector Strips shall be Underwriter Laboratories (UL) and Canadian Underwriter
Laboratories (cUL) LISTED.
B) Physical
1) Connector strips shall be 6.25” H x 3.3” D and fabricated from 18-gauge galvanized
steel and finished in black fine-texture powder coat paint.
a) Covers shall be fabricated from 16-gauge galvanized steel
2) Connector strips shall be available in any length specified in increments of 6” and
shipped fully wired with all splicing hardware.
3) Pigtails and outlets shall be spaced on 18” centers, or as otherwise specified.
4) Outlets shall be mounted on individual 3” panels and there shall be
5) No external terminal boxes shall be required for connector strips with 28 or fewer
circuits unless otherwise specified.
6) Circuits shall be labeled on the connector strip with 2” lettering.
a) Circuit labeling options shall include:
1) Circuits shall be labeled on the front side of the connector strip with white
lettering on black background labels.
2) Circuits shall be labeled on front and back sides of the connector strip
with white lettering on black background labels.
3) Circuits shall be labeled on the front side of the connector strip with
engraved lamicoid labels utilizing white lettering on black background labels.
4) Circuits shall be labeled on the front and rear sides of the connector strip
with engraved lamicoid labels utilizing white lettering on black background
labels.
5) Circuits shall be labeled on one side of the connector strip using
individual circuit cover plates with lettering engraved in the cover and filled
with the specified color.
6) Circuits shall be labeled using specified labeling per plans and drawings