266 Chapter 23 Dimmer monitoring
Load Check procedure
Load Check compares the current load on selected dimmers with their
recorded loads. The system checks load information only for selected
dimmers. To identify the dimmer(s) you wish to check, use either the
console or the CEM to set the desired dimmers at a level above zero.
The system checks 24 dimmers per rack at a time until all dimmers at
levels above zero have been checked. If you have multiple racks, 24
dimmers in each rack are checked simultaneously.
109
Caution
: Load Check changes levels on stage. Dimmer outputs rise and
fall for several minutes during the procedure. To cancel a check load
operation in progress, press [S7],
Cancel
, [Enter].
Follow these steps to check loads for your system:
109.
On single phase racks, the system checks 16 dimmers per rack at a time.
Keystrokes:
Action:
1. Set dimmers to be
checked to a level above
zero. Only dimmers above
zero are checked.
a
a. If you wish, instead of setting the desired dimmers to a level
in step 1, you may enter a list of dimmers to record in step 5.
2. Press [Setup].
Selects Setup display
3. Select [9], ETCLink
Functions, and press
[Enter].
Selects ETCLink Functions menu
4. Select [4], Load
Management, and press
[Enter].
Selects Load Management display
5. Press [S4], Load Check.
(You may enter specific
dimmers to check.)
Prompt reads:
To check loads, select dimmer(s)
and press ENTER (Enter 0 to check
loads for all dimmers)
6. Press [0] [Enter] [Enter].
Advisory reads:
All dimmers with levels above zero
will have their loads checked.
Levels on stage will change while
the Load Check is in progress. The
system will automatically vary the
dimmer outputs during the Load
Check. The process may take
several minutes to complete.
7. Press [Enter] to proceed
with the load check, or
press [Clear] to cancel the
operation.
Loads are checked for all dimmers
with levels above zero
Once complete, advisory reads:
Load check processing has
completed
Press [Clear] to continue